For safety, the inverter and motor must be well-grounded, as leakage current may exceed 3.5mA. 2. Wiring and Technical Specifications
Set the primary speed adjustment method (e.g., keypad, digital setting, or analog input). Confirm: Press ENTER after modifying any value. 4. Troubleshooting and Maintenance
If the inverter encounters an issue, the display will flash a fault code. Regular inspection of motor insulation (minimum 5MΩ) is recommended to prevent secondary inverter damage. 用户手册 Jte Inverter Manual
Before mounting the device, ensure the environment meets these critical standards to prevent equipment damage or fire risks:
JTE Inverter User Manual: Installation, Operation, and Troubleshooting For safety, the inverter and motor must be
Proper wiring is vital for operational stability. Always disconnect input power before starting work. Standard Specifications (Typical 380V Models) AC 380V 3-phase (-15% to +10%) or 220V single-phase MPPT Range 450VDC–750VDC for 380VAC models Output Frequency 0–50Hz/60Hz Overload Capacity 150% for 1 minute; 180% for 10 seconds Key Wiring Rules:
For most JTE models, such as the , the control panel is used for initial configuration: Enter Programming: Press the PRGM key. Confirm: Press ENTER after modifying any value
Maintain an ambient temperature between -10°C and 50°C. For altitudes above 1,000 meters, derate the output current by 1% for every 100 meters.